Peek Measurement  
 
http://www.thermomeasurement.com

Alarm Monitoring Systems

Spare parts local inventory
Repair service for electronic cards and components
Technical service through original manufacturer engineers

Main Characteristics:

- 6, 12, 24, channel cards
  communicating  
  simultaneously with a 
  Central Monitor Card.
- Response time less than
  0,8 s programmable up 
  to  60 s.
- Threshold and rate alarms
  can be configured as 
  required to operate either
  of two common alarm relays
  supplied as standard. 
  These  relays are
  connected directly to the
  internal bus system and 
  are therefore immune 

Alarm Monitor Series 4000
Alarm Monitor Series 4000

  from any failure of the monitor card or even its incomplete removal from the
  system
- The 4400 offers maximum user control in defining how relays will operate on
  alarm. By this means, relay outputs can be grouped by function to provide
  selective closures to external devices such as PC's, PLC's, DCS's, or
  annunciators. They can be configured for reflash or klaxon sequences,
  depending on the application. Two relays can also be optionally fitted to 
  any channel card to provide per-points contacts.
- Optional DC analogue re-transmission output per channel. 0 to 10mA, 0 to
  20mA, 4 to 20mA; Accuracy 0,1% span. Output either directly proportional
  to input signal or linearised to temperature, using International Standard
  sensor characteristics, or linearised to a user-entered characteristic.
- Up to 1 A at 24 VDC available on rear terminals for powering transmitters.
  Protecting by self re-setting fuse.
- Dead band: adjustable 0 to 25% of span in 1% increments individually for
  each set-point.

Internal Clock

- Internal log-book for event registrations. Possibility to visualize on the
  display all past events.

Self-analysis

- Internal diagnostic system for fault self-identification.

Flexibility

- Menu configuration
- Fully configurable form the front panel. (Possibility to copy channel
  configuration from channel to channel)
- Password
- The measured variable for any selected channel is displayed with 
  engineering unit annotation and user-tagging where appropriate. Alarm
  set-point information is also continuously shown. If desired, a display
  scanning sequence can be initiated, with user control of speed and channel
  to be displayed.
- "Reset relay" function

External Interfaces

- Optional serial connection (RS232 o RS485) to an external PC for data
  downloading.

Technical Info

Power supply

6 channels
12 channels
24 channels

24VDC
(18-35V)
35W
45W
65W
110/220VAC
50/60Hz
45VA
55VA
75VA

Environmental compliant with requirements of EN61010-1
Temperature range 0°C to 50°C

Front panel
Humidity
Vibration
Shock
IP54
0-95% RH in accordance with the requirements me IEC 68-2-3
Tested in accordance with IEC-2-6
Drop tested to IEC 68-2-31

Complies with requirement of EN 50081-1 emissions and EN 50082-2 Immunity

Input

Sensor Range Thermocouple Range Input Range
RTD   J -180°C a 750°C Ohm 0 a 450
Pt100 µ0.0385W/° -200°C a 850°C K -200°C a 850°C mA -10mV a 100mV
Pt100 µ0.0392W/° -200°C a 645°C T -200°C a 645°C V 0V a 1V
Ni120 -70°C a 300°C E -60°C a 1000°C V 0V a 1V
Cu10 -50°C a 250°C N -0°C a 1210°C V 0V a 1V
Cu30 -50°C a 25°C R -0°C a 1600°C mA 4mA a 20 mA
Pt20 -50°C a 25°C S -0°C a 1560°C mA 0mA a 10ma
    L -200°C a 900°C mA 0mA a 20mA
    U -200°C a 600°C    

Digital accuracy 0.5°C (RTDs) 1,0°C (T/C) or 0,1% span (Analogue input).

Dimension (mm)

Model Front Panel Panel cut-out Panel cut-out Nominal
  Width A Width Height Weight (Kg)
6 Channels 192 186 (+10 - 0) 186 (+10 - 0) 6,4
12 Channels 288 282 (+10 - 0) 186 (+10 - 0) 9